Vertical Circuit Switchers

Circuit Switchers – Vertical (CSV, CSV-CB-DB)

Southern States’ CSV (“candlestick”) circuit switcher, with vertical interrupters, is designed specifically for transformer protection and switching applications where substation space is limited. Unlike traditional general purpose circuit breakers, these devices account for the fast rate-of-rise transient recovery voltage (TRVs) during the interruption of a transformer limited fault.

Additionally, the CSV can be integrated with a Southern States disconnect switch. Most commonly, these designs include an integral double sidebreak “vee” switch (CSV-DB) or an integral center break “vee” switch (CSV-CB). Both can be specified for manual or motor operation.

CSV 245kV
SRP Carrel Substation CSV Photos
CSV69kVsinglepedestalunits.jpeg
CSV-DB115-40-2000.jpeg
previous arrow
next arrow
CSV 245kV
SRP Carrel Substation CSV Photos
CSV69kVsinglepedestalunits.jpeg
CSV-DB115-40-2000.jpeg
previous arrow
next arrow
 

  • Compared to dead tank circuit breakers, circuit switchers have a significantly smaller footprint and utilize significantly less SF6
  • Simple, easy erection minimizes field installation time required.
  • Structure baseplate can have its hole locations and hole sizes varied when required to fit existing foundation locations and anchor bolt sizes.
  • Gas density switch with low pressure alarm and low pressure lockout contacts allow remote gas monitoring.
  • Local visual indication of gas system by an SF6 pressure gauge.
  • Ships with minimal gas pressure for safety during transportation and in handling during installation.
  • Adaptable to a wide variety of installation height requirements and foundation requirements.
  • 4 hole NEMA terminal pads are readily reversible to fit specific installation requirements.
  • Each unit is completely assembled and tested at the factory with only the disassembly required to meet shipment restrictions being performed
Choose Voltage Rating:
Maximum kV Rating27383848.372.53848.372.5
BIL (kV)150200200250350200250350
Continuous Current1200 A & 1600 A1200 A1200 A, 1600 A, 2000 A, 2500 A
Primary Fault Interrupting25 kA25 kA (31 kA*)40 kA
Secondary Thru-Fault Interrupting4 kA4 kA4 kA
Interrupting Time3 cycles5 cycles3 cycles
Power Frequency50/60 Hz60 Hz60 Hz
Short-Time Withstand25 kA (3 sec)40 kA (3 sec)40 kA (3 sec)
Peak Withstand62.5 kA104 kA104 kA
Short-Circuit Making25 kA40 kA40 kA
Insulator DesignPorcelainCompositePorcelain
Ambient Temperature Range-40º C to +50º C-40º C to +50º C
(-50º C to +50º C optional)**
-30º C to +50º C
* Product can be rated for 31.5 kA interrupting (3 operations)
** -50º C rating is 18 kA (SF6 / N2)