Gold Eagle

Single-Phase Cutout-Mounted Recloser

The industry’s first solar-harvesting cutout recloser

This solar-powered cutout-mounted recloser reduces outages and maintenance — with battery-free, sustainable operation.

Southern States’ Gold Eagle Cutout-Mounted Recloser is the industry’s first solar-harvesting cutout recloser, revolutionizing reliability, efficiency, and cost savings for utilities. Designed to mount directly in standard cutout, it streamlines inventory management with uniform ratings and a plug-and-play footprint that fits seamlessly into existing systems.

Its dual power source — combining line current energy harvesting and an integrated solar panel — enables sustainable, battery-free operation. With advanced technology and intuitive design, the Gold Eagle reduces outages, streamlines maintenance, and enhances overall system reliability.

Key Benefits:

  1. Fits in standard cutouts for easy installation and inventory simplification
  2. Stays securely in the fuse holder after lockout– does not “fall out”
  1. Manually removable with hot stick if air gap is required
  1. Dual power sources – line energy harvesting + solar panel harvesting
  1. 1.5A minimum charge current
  2. 36-hour dead time operation
  1. Local hot stick operation through yellow handle or remote operation through USB dongle
  2. Red/green semaphore and blinking LED for device status indication
  3. Abundance of protection curves – IEC, IEE, hydraulic, fuse, and more
  4. Optional SCADA cabinet
  5. Helps reduce outages and streamline field maintenance
  6. Backed by Southern States' 24/7 after-sales support and long-life engineering

Product Family

Gold Eagle™ Single-Phase Cutout-Mounted Recloser

Single-Phase Cutout-Mounted Recloser

  • Maximum Voltage: 15kV
  • Continuous Current: 300A (200A above 50C)
  • Interrupting Current: 6.5kA
Maximum Voltage15.5 kV
Basic Insulation Level (BIL) Max.110 kV
Continuous Current300 A (200 A Above 50°C)
Interrupting Current RMS6.5 kA
Weight25 lbs
Interruption MechanismVacuum / Magnetic Actuator
Minimum Charging Current1.5 A
Minimum Trip Current3 A
Voltage DetectionAbsence / Presence
*