Horizontal Circuit Switchers

The most versatile and capable Horizontal Interrupter Circuit Switchers in the marketplace today.

The Southern States family of horizontal interrupter circuit switchers are ideally suited for transformer protection on systems with fault currents up to 40 kA. All circuit making and breaking operations are accomplished in SF6, eliminating open air arcs.

Designs are available with an integral vertical break switch (Types CSH-B or CSH2-B) or without (Types CSH or CSH2) and are extremely versatile, as they can be mounted in most orientations including horizontal upright and vertical. In addition, they can be designed to mount on a customer or Southern States supplied support structure as well as existing structures.

The CSH(2)-B is ideal for mobile applications with a rating up to 40kA. The use of composite interrupters will allow for pressurized transport without special protective housing.

CSH-B121-20-1200andCSV725-315-2000.jpeg
CSH-B230kV.jpeg
145kVCSH-B.jpeg
CSH-B Mobile
CSH-B230-20-1200.jpeg
CSH-B Mobile(2)
CSH-B230-20-1200HooverDam.jpeg
CSH-B161-20-1200.jpeg
previous arrow
next arrow
CSH-B121-20-1200andCSV725-315-2000.jpeg
CSH-B230kV.jpeg
145kVCSH-B.jpeg
CSH-B Mobile
CSH-B230-20-1200.jpeg
CSH-B Mobile(2)
CSH-B230-20-1200HooverDam.jpeg
CSH-B161-20-1200.jpeg
previous arrow
next arrow
 

  • Makes and breaks circuit in SF– No open air arcs
  • Available with and without vertical break disconnect
  • Visual dielectric indication
  • Can be shipped pressurized when composite housing is specified or protective shields for porcelain housing are utilized
  • Adaptable to a wide variety of mounting positions, structure heights, and phase spacings
  • Ideally suited to upgrade fault interrupting capability of existing horizontal circuit switchers, disconnect switches, and power fuses, reusing the existing structure and foundation.
Choose Voltage Rating:
BLADE BIL RATINGS (FOR CSH-B)
Max Voltage38 kV48.3 kV72.5 kV123 kV145 kV170 kV
Blade BIL200 kV250 kV350 kV550 kV650 kV750 kV
550 kV BIL INTERRUPTER RATINGS*
Temp Range1≤ 72.5 kV123 kV
PBF 100s-30° C to +50° C20 kA
-40° C to +50° C25 kA
-50° C to +40° C15 kA 512 kA 5
TLF-40° C to +50° C4 kA 2.9 kA 2
-50° C to +40° C2.5 kA 51.7kA 5
  1. Ratings shown are for 1200A. For 1600A, top temp is +40°C.
  2. Nameplate will include note “TLF = 4 kA @ 7.6 kV/µs TRV”
  3. Ratings do not apply to 2000A.
  4. Ratings apply to both porcelain and composite interrupter housings
  5. SF6 / N2 Gas Mixture
  6. All ratings are suitable for ungrounded systems (1.5 kpp)
750 kV BIL INTERRUPTER RATINGS*
Temp Range≤ 72.5 kV123 kV145 kV***170 kV 6
PBF 100s-40° C to +50° C25 kA20 kA 3
-50° C to +40° C15 kA 712 kA 7
TLF**-40° C to +50° C4 kA2.9 kA 22.3 kA 22.7 kA 2
-50° C to +40° C2.5 kA 71.7 kA 71.4 kA 71.6 kA 7
  1. Ratings shown are for 1200A. For 1600A, top temp is +40°C.
  2. Nameplate will include note “TLF = 4 kA @ 7.6 kV/µs TRV”
  3. The 123 kV can also be rated 25 kA for -30°C to +50°C. Existing installation only. If 25 kA is specified for a new installation, the CSH2 design should be utilized.
  4. Ratings do not apply to 2000A.
  5. Ratings apply to both porcelain and composite interrupter housings
  6. 170 kV ratings are for grounded systems (1.3kpp)
  7. SF6 / N2 Gas Mixture