Horizontal Circuit Switchers (CSH, CSH-B)

The most versatile and capable Horizontal Interrupter Circuit Switchers in the marketplace today.

The Southern States CSH and CSH-B horizontal interrupter circuit switchers are ideally suited for transformer protection providing up to 40kA primary fault clearing capabiltiy and 4kA secondary through fault clearing capability. All circuit making and breaking operations are accomplished in SF6, eliminating open air arcs. The horizontal interrupter circuit switcher is available with (Model CSH-B) or without (Model CSH) an integral vertical break switch.

The design of the CSH and CSH-B is extremely versatile and can be mounted in most any orientation including horizontal upright, vertical, and underhung positions. It can also be designed to mount on a Southern States supplied support structure or for mounting on a customer supplied or existing structure. The CSH-B is also ideal for mobile applications and can be supplied with composite interrupters that can be shipped pressurized.

In addition to transformer protection, the CSH and CSH-B can be used for line dropping, loop splitting, or as a series capacitor/reactor bypass switch.

Add to quote cart
Angled_jaw_end_view_of_csh-b_230-20-1200_at_hoover_dam

CSH-B 230-20-1200 (Hoover Dam)

  • Angled_jaw_end_view_of_csh-b_230-20-1200_at_hoover_dam
  • Close_up_angled_shot_of_csh-b_230-20-1200
  • Closer_profile_view_of_csh-b_138-20-1200
  • Csh-b_121-20-1200_and_csv_72
  • Csh-b_230-20-1200
  • High_angle_view_looking_downward_at_csh-b_161-20-1200

CSH & CSH-B Horizontal Interrupter Circuit Switcher Family Overview

Maximum kV Rating 38 kV - 170 kV 245 kV
Primary Fault Interrupting 25 kA to 40 kA 20 kA
Interrupting Time 5 cycle 6 cycle
With Integral Disconnect Yes (CSH-B) No (CSH) Yes (CSH-B) No (CSH)
  • Circuit made inside the interrupter – No open air arcs
  • Available with and without vertical break disconnect
  • Visual dielectric indication
  • Standard porcelain interrupter ships with minimal gas pressure for safety during transportation and in handling during installation. Can be shipped pressurized when composite housing is specified or protective shields are utilized
  • Adaptable to a wide variety of mounting positions, structure heights, and phase spacings
  • Ideally suited to upgrade fault interrupting capability of existing horizontal circuit switcher installations (all Mfgs), reusing the existing switcher’s structure and foundation.
  • The only 40kA circuit switcher available for mobile applications.
  • Southern States 5-year warranty promises trouble-free operation
Maximum kV Rating 38 48.3 72.5 123 145 170
Interrupter/Blade BIL (kV) 550*/200 550*/250 550*/350 550* 650 750
Continuous Current 1200 A & 1600 A for all kV ratings
Primary Fault Interrupting 25 kA, 31.5 kA, and 40 kA for all kV ratings*
Interrupting Time 5 cycles
Power Frequency 60 Hz
Short-Time Withstand 40 kA / 1 sec
Peak Withstand 108 kA
Short-Circuit Making 40 kA
Ambient Temperature Range -40º C to +50º C standard
-50º C to +50º C optional

* For 38 kV thru 123 kV the standard interrupting ratings are 25 kA or 31.5 kA. If a 40 kA interrupting rating is required, the 650 kV BIL interupter will be utilized.

Maximum kV Rating 245
Interrupter/Blade BIL (kV) 900
Continuous Current 1200 A & 1600 A
Primary Fault Interrupting 20 kA (12 kA for -50º C)
Interrupting Time 6 cycles
Power Frequency 60 Hz
Short-Time Withstand 40 kA / 1 sec
Peak Withstand 108 kA
Short-Circuit Making 40 kA
Ambient Temperature Range -30º C to +50º C standard
-50º C to +50º C optional

Power Transformer Switching and Protection

Mobile Substations

Line Dropping or Loop Splitting

Series Reactor/Capacitor Bypassing

Transformer Protection and Switching

Power Transformer Switching and Protection

Mobile Substations

Line Dropping or Loop Splitting

Series Reactor/Capacitor Bypassing

Transformer Protection and Switching